HRDS Series

HRDS421

  • Product Literature
    • Electrical Characteristics
      • Catalog # HRDS421
      • Input Voltage (V) 120 V ac
      • Input Tolerance (%) -20% - 10%
      • Input AC Line Frequency (Hz) 50/60
      • Output Type Electromechanical relay
      • Output Form Non-isolated SPDT
      • Output Load Rating (VA) General Purpose: SPDT-NO: 125/240 V ac ≅30 A; SPDT-NC ≅15 A; Resistive: SPDT-NO ≅30 A for 125/240 V ac and 20 A for 28 V dc; SPDT-NC ≅15 A for 125/240 V ac and 10 A for 28 V dc; Motor Load: SPDT-NO ≅1 hp for 125 V ac and 2 hp for 240 V ac; SPDT-NC ≅1/4 hp for 125 V ac and 1 hp for 240 V ac
      • Time Delay Type Microcontroller
      • Time Delay Range 1 - 100 s onboard adjustable
      • Time Delay Tolerance (%) ±5%
      • Reset Time (ms) ≤150
      • Initiate Time (ms) ≤20
      • Repeat Accuracy (%) ±0.5% or 20 ms whichever is greater
      • Setpoint vs Ambient Temperature and Operating Voltage (%) ≤±2%
      • Surge Protection IEEE C62.41-1991 Level A
      • Insulation Resistance ≥100
      • Dielectric Breakdown ≥2000V terminals to mounting surface
      • Circuitry Encapsulated
      • Life Electrical: 1 x 10⁵ 3 x 104 for 1 hp - 6000 for 1/4 hp 1 hp and 2 hp; Mechanical: 1 x 10⁶
      • Power Consumption ≤4 VA
      • Termination Type 0.25 in. (6.35 mm) male quick connect terminals
      • Mounting Method Surface mount with 1 #10 (M5 x 0.8) screw
      • Operating Temperature -40° to 60°C (-40° to 140°F)
      • Storage Temperature (F/C) -40° to 85°C (-40° to 185°F)
      • Humidity 95% relative : non-condensing
      • Dimensions 3 H x 2 W in. (76.7 x 51.3 mm)
      • Weight (lbs/g) 0 Kg
      • Dimensions 3 H x 2 W in. (76.7 x 51.3 mm)