  • Product Literature
    • Electrical Characteristics
      • Catalog # LLC14A5AX
      • Input Voltage (V) 120 Vac
      • Input Tolerance (%) -0.3
      • Input AC Line Frequency (Hz) 50 / 60
      • Output Type Electromechanical relay
      • Output Form Non-isolated SPST and isolated SPDT contacts
      • Output Load Rating (VA) 10 A resistive @ 120/240 Vac and 28 Vdc; 1/3 hp @ 120/240 Vac
      • Time Delay Range 5 s fixed
      • Sense Voltage Low voltage AC between probe and common; isolated from input and ouput
      • Sense Resistance (Ohms) Adjustable to 250
      • Sense Resistance Tolerance Guaranteed range
      • Control Type ON/OFF (single level) resistance sensor with built-in time delay to prevent rapid cycling
      • Isolation voltage ≥1500 Vrms between input; output; and probe
      • Surge Protection IEEE C62.41-1991 Level A
      • Termination Type 0.25 in. (6.3 mm) male quick connect terminals
      • Mounting Method 0.50 in. (12.7mm) nylon standoffs with three #6 (M3.5 x 0.6) screws (use terminal 5 for probe common)
      • Operating Temperature -20° to 55°C (-4° to 131°F)
      • Storage Temperature (F/C) -40° to 80°C (-40° to 176°F)
      • Dimensions 3.5 H x 2.75 W x 2 D in. (88.9 x 69.9 x 50.9 mm)
      • Weight (lbs/g) 0 Kg
      • Check Stock Yes