233P

233P-1.5-ENCL

  • Electrical Characteristics
    • Catalog # 233P-1.5-ENCL
    • Input Voltage (V) 230 Vac
    • Maximum Input Power 5
    • Input AC Line Frequency (Hz) 50 / 60 (50 will increase all delay timers by 20%)
    • Input Load Range (hp) 1/3 - 1.5
    • Output Form SPST
    • Output Load Rating (VA) 1.5 hp @ 240 Vac (10 A max.)
    • Rapid Cycle Timer (s) 4 restarts allowed in 60 s period
    • Restart Delay Range Over/Under Voltage: 2 s; All other faults: Manual; 2 - 225 m
    • Trip Delay Range Overcurrent: 5 s; Dry-well: 4 s
    • Overvoltage Trip Voltage (%) 265 Vac
    • Undervoltage Reset Voltage (%) 190 Vac
    • Overcurrent Trip Class 125% of calibration point
    • Underload (%) Adjustable (70 to 90% of calibrated run power)
    • Termination Type Torque: 13 in-lbs; Wire: Solid or stranded 10 - 22 AWG
    • Mounting Method #8 screws
    • Operating Temperature -40° to 55°C (-40° to 131°F)
    • Dimensions 8.3 H x 5.36 W x 3.68 D in. (210.8 x 136.1 x 93.5 mm)
    • Weight (lbs/g) 0 Kg
    • Check Stock Yes