111P

111P

  • Product Literature
    • Electrical Characteristics
      • Catalog # 111P
      • Input Voltage (V) 115 Vac
      • Maximum Input Power 5
      • Input AC Line Frequency (Hz) 50 / 60 (50 will increase all delay timers by 20%)
      • Input Load Range (hp) 1/3 - 1
      • Output Form SPST
      • Output Load Rating (VA) 1 hp @ 120 Vac (16 A max.)
      • Rapid Cycle Timer (s) 4 restarts allowed in 60 s period
      • Restart Delay Range Over/Under Voltage: 2 s; All other faults: Manual; 2 - 225 m
      • Trip Delay Range Overcurrent: 5 s; Dry-well: 4 s
      • Overvoltage Trip Voltage (%) 132.5 Vac
      • Undervoltage Reset Voltage (%) 95 Vac
      • Overcurrent Trip Class 125% of calibration point
      • Underload (%) Adjustable (70 to 90% of calibrated run power)
      • Termination Type Torque: 13 in-lbs; Wire: Solid or stranded 10 - 22 AWG
      • Mounting Method #8 screws
      • Operating Temperature -40° to 55°C (-40° to 131°F)
      • Dimensions 2.93 H x 5.25 W x 2.91 D in. (73.7 x 133.4 x 74 mm)
      • Weight (lbs/g) 0 Kg
      • Check Stock Yes