250A

250A

  • Product Literature
    • Electrical Characteristics
      • Catalog # 250A
      • Input Voltage (V) 190 - 480 Vac
      • Maximum Input Power 5
      • Input AC Line Frequency (Hz) 50 / 60 (50 will increase all delay timers by 20%)
      • Output Form DPDT - 2 Form C
      • Output Load Rating (VA) Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac
      • Restart Delay Range Manual; 2 - 300 s adjustable
      • Trip Delay Range Under/Over Voltage: 4 s; Unbalance/Phase faults: 2 s
      • Trip Point Accuracy (%) ±1%
      • Overvoltage Trip Voltage (%) 110%
      • Overvoltage Reset Voltage (%) 107%
      • Undervoltage Trip Voltage 90%
      • Undervoltage Reset Voltage (%) 93%
      • Voltage Unbalance Trip Point (%) 6%
      • Voltage Unbalance Reset (%) 4.50%
      • Termination Type Torque: 7 in-lbs; Wire Size: 12 - 18 AWG
      • Mounting Method #8 screws
      • Operating Temperature -40° to 70°C (-40° to 158°F)
      • Humidity Up to 95% non-condensing per IEC 68-2-3
      • Dimensions 2.93 H x 5.27 W x 2.95 D in. (94.4 x 133.9 x 74.9 mm)
      • Weight (lbs/g) 0 Lb
      • Check Stock Yes